Free ball float type steam trap


A, function and characteristics

1, continuous drainage, water discharge, improve the heat transfer efficiency of equipment.

2, stop gas tight, low leakage rate (< 0.3%), good energy saving effect.

3, the filter area is big, not easy to be blocked, no wearing parts, long service life (> 16000 hours).

4, small volume, stable running, no noise.

Two, technical characteristics table two

Nominal pressure model (MPa) working pressure (MPa) leakage rate (%) pressure rate (%) maximum flow rate (T/h) service life (time) three points support free floating ball type steam hydrophobic valve 1.62.54.0 200 (cast iron) 300 (cast iron < 0.3 < 800 > 16000

Three, models, specifications

Table two

Model

Nominal pressure

(MPa)

Nominal diameter

(mm)

Maximum capacity

(T/h)

Shell material

S11H-16

1.6

15, 20, 25, 40

0.6

Cast iron

Thread

S41H-16

15, 20, 25, 32, 40

0.6

Flange JB/T81-94

S11H-16C

40, 50, 65, 80, 100

2.6

S41H-16C

15, 20, 25

0.6

Cast steel

Thread

15, 20, 25, 32, 40

0.6

Flange JB/T81-94

S11H-25

1.6

40, 50, 65, 80, 100

2.6

15, 20, 25

0.4

Thread

S41H-25

2.5

15, 20, 25, 32, 40, 50

0.4

Flange JB/T81-94

40, 50, 65, 80, 100

1.6

S41H-40

4

15, 20, 25, 32, 40, 50

0.3

40, 50, 65, 80, 100

1.2

Four, sketch and installation size

Five, steam traps installed

1, the installation of hydrophobic valve shell (or plate) arrow mark and the condensed water flow to the same. Traps should be installed horizontally, keep upright or inclined. Dual chamber type drain valve can be designed according to user needs vertical mounting structure.

2, hydrophobic valve should be added before the need for maintenance of reference, steam trap valve installation diagram. During normal operation, the by-pass valve is closed, the inlet valve open. Maintenance bypass valve to open, close inlet valve.

3, the lowest hydrophobic points should be arranged in the equipment or pipeline.

4, the trap should be as close as possible to the heat exchange equipment installation.

Six, selection of steam trap

The correct selection is the prerequisite to use traps, select trap should focus on the following points:

1, the hydrophobic point of the maximum working pressure and the maximum operating temperature, to determine the nominal pressure rating and shell material of trap, according to connection can determine trap model.

2, according to the drainage point condensation water discharge elimination, multiplied by 2-5 times the magnification is the selection of steam trap discharge.

3, steam pipe and a siphon outlet heat exchanger should use double cavity type steam hydrophobic valve.

4, a heat exchange equipment shall be installed a trap, not several heat exchangers share one (or a few) trap.

 
 